Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL |
|
| 04/12/2006 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/11/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 240 VOLT UNITS REQUIRE MIN. 46 AMP. FUSES. 45 AMP IS TOO SMALL. DO NOT USE INK TO MARK THE UNIT DATA PLATES. SCRATCH OUT THE BLACK BOX JUST LIKE THE DATA PLATE TELLS YOU TO. CIRCUIT BREAKERS DO NOT MEET MIN. REQUIREMENTS. |
|
| 04/05/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE ROOF JACKS AT CONDENSATE PENETRATIONS. WORK UNIT DATA PLATES W/PROPER HEAT KIT INSTALLED & FUSE ACCORDINGLY. BLOCK & CLAMP EXPOSED PVC MAX. 4' INTERVALS & PAINT W/LATEX PAINT REPAIR BROKEN CONDUIT UNIT 1 AT DISCONNECT. REPLACE DRYER VENT UNIT 1 |