Permit: T05CM02427

Parcel: 11006048E

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/14/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
04/12/2006 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
04/11/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
240 VOLT UNITS REQUIRE MIN. 46 AMP. FUSES.
45 AMP IS TOO SMALL.
DO NOT USE INK TO MARK THE UNIT DATA PLATES.
SCRATCH OUT THE BLACK BOX JUST LIKE THE DATA PLATE TELLS YOU TO.
CIRCUIT BREAKERS DO NOT MEET MIN. REQUIREMENTS.
04/05/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE ROOF JACKS AT CONDENSATE PENETRATIONS.
WORK UNIT DATA PLATES W/PROPER HEAT KIT INSTALLED & FUSE ACCORDINGLY.
BLOCK & CLAMP EXPOSED PVC MAX. 4' INTERVALS & PAINT W/LATEX PAINT
REPAIR BROKEN CONDUIT UNIT 1 AT DISCONNECT.
REPLACE DRYER VENT UNIT 1