Inspection History: ELECTRIC - OUTDOOR LIGHTING

Date Description Inspector Results Comments
04/19/2006 ELECTRIC - OUTDOOR LIGHTING Approved IVRS - Inspection :*
04/05/2006 ELECTRIC - OUTDOOR LIGHTING Not ready for Inspection IVRS - Inspection :*
1) RECEPTACLE COVERS TO BE WEATHER PROOF WHETHER OR NOT PLUGGED IN 406.8
2) A CONNECTOR IS NEEDED AT HOOD
3) SWITCHES TO BE GROUNDED
4) BREAKER TO BE SIZED PER AMPACITY ON NM CONDUCTOR 330.80
5) A DISCONNECTING MEANS IS NEEDED FOR WATER HEATER
6) PLEASE ADD 02090 TO PERMIT