Permit: T05CM02414

Parcel: 10511040D

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
12/12/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1. CLOSET FLANGE OK - OK TO COVER ALL AREAS
11/14/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/10/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*PLEASE POST YOUR SUITE NUMBER
HORIZ X HORIZ. CHANGE OF DIRECTION TO BE A SWEEP
HANGERS ARE REQUIRED AT :
EACH CHANGE OF DIRECTION
EACH CHANGE OF ELEVATION
AT THE END OF BRANCHES
THEN NO MORE THAN 4" ON ABS
6'-8' ON COPPER, ETC
NEED TO SEE CLOSET FLANGES
DON'T FORGET VERTICAL SUPPORT
NO UNIONS ABOVE T-BAR
11/07/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*