Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM02414
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/19/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/13/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK TO ENERGIZE SERVICE NOTE: BOND METER RACEWAY SCOTT HAWORTH. CORP POST POWER BOND # 650365 ON 12/12/05 OK TO CLEAR RTM NOT ON COMPUTER SCREEN YET |
|
12/09/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
12/05/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK TO COVER ELECTRICAL IN CEILING ( REAR AREA'S) NOTE: LEAVE ONE TILE OFF EACH AREA SO I CAN SEE REMAINING WORK. |
|
11/14/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK TO COVER ELECTRICAL IN CEILING ( HARD LIDS IN FRONT) | |
11/09/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO COVER ELECTRICAL IN WALLS |
|
11/07/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*USE LISTED STRAPS FOR ALL FLEX & CONDUIT PROPERLY SUPPORT ALL BOX'S NOTE OK TO COVER ONE SIDE OF INTERIOR WALLS |
|
10/14/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*UG PANEL FEEDERS |