Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 11/01/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) NEED DWV AND POTABLE H20 TEST 2) STRAP GAS LINE ATTIC 3) ELECTRIC FOR 2ND FLOOR BATH NOT COMPLETE 4) #4 SHEARWALL REQUIRES 1/2" DIAMETER A.B. AT 48" ON CENTER 5) 8D NAIL IN 1ST FLOOR LAV VERT/DRAIN 6) REPLACE DRYER DUCT 7) ROMEX TO 1ST FLOOR EXHAUST FAN UNDER STAIR 8) CONSULT WITH POST TENSION ENGINEER, REF 2" VENT FOR WEST TOILET AND SHOWER, CONC. CUT AT EDGE/PERIMETER FTG 7) STAPLE IN 1" H20 LINE AT H20 HTR 8) FREON LINE STAPLE KIT WALL |