Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM02406
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/26/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/24/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BOND JUNCTION BOX FOR GROUNDING CONNECTIONS AND IDENTIFY JUMPER CONDUCTOR 2) FILL UNUSED OPENINGS IN JUNCTION BOXES AND BOND BOX 250.148 3) PLEASE VERIFY LISTING OF CABINET WITH LIGHTING 4) APPROVED EXTENDER RINGS ARE NEEDED FOR BOXES MORE THAN 1/4" IN NON-COMBUSTIBLES AND FLUSH IN COMBUSTIBLES 314.20 5) WHERE IS GROUNDING CONDUCTOR TO X-RAY GENERATOR AS PLANS 6) FINISH X-RAY ON LIGHTS 7) NOTE FROM LAST INSPECTION REGARDING VDV CABELING |
|
09/18/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BOND BUSHINGS NEEDED AT CONCENTRIC OVER 250 V - 250.97 2) FINISH WALLS AT PHILLIPS CONTROL ROOM * VDV CABLING TO BE AS PLAN 725.6, 760.6, 800.6 OK WALLS AND HARD CEILING ANGLO ROOM EXCEPT AS NOTED |