Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOOD SYSTEMS
Permit Number - T05CM02399
Inspection Description - MECHANICAL - HOOD SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2005 | MECHANICAL - HOOD SYSTEMS | Approved | IVRS - Inspection :*REMOVE EXTRA TEES FROM GAS LINE OR REVISE PLANS GAS SHUT OFF VALVES MUST PRECEDE THE UNION. RETEST SYSTEM. PROVIDE SUPPORT ON DUCT ON ROOF. FINISH CONNECTING A/C UNIT. ELEC. DISONNECT IS BLOCKING ACCESS PANEL ON EVAP. COOLER.PERMANENTLY LABEL ALL EQUIPMENT REMOVE ABANDONED EQUIPMENT ON ROOF PLUMBING GAS PRESSURE TEST HAS BEEN ADDED TO THE PERMIT. PAY THE EXTRA 7.00 FEE AT D.S.D |