Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 11/28/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLUG OPEN KNOCKOUT IN BOTTOM OF SERVICE PANEL 2) CLEAN INSIDE OF PANEL-REMOVE COMBUSTIBLES 3) A/C WHIP REQUIRES CLAMP 12" FROM DISCONNECT 4) INSTALL A/C FUSES 5) BUBBLE COVER REQUIRED AT REAR EXTERIOR RECEPTACLE-WET LOCATION 6) STOPPED INSPECTION |