Permit: T05CM02380

Parcel: 11306129E

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
07/27/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
07/20/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 3" BLDG DRAIN AND 3" BLDG SEWER TO POINT OF CONNECTION TO 4" SEWER WATER TEST OK
2) 1" BACKFLOW DEVICE AT METER TO (2) 3/4" SERVICES TO BLDG WATER TEST OK
3) NEED TO REMOVE TEE CONNECTION BETWEEN METER AND PRIMARY BACKFLOW DEVICE AND PROVIDE INSPECTION OF THIS
06/23/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) ABS DWV FOR TOILET ROOM AT BLDG #3 OK TO COVER
2) RECALL 3005 ROUGH/SOIL FOR SEWER INSPECTION