Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/01/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING. 514.20 METAL NOT APPROVED 2) WHERE IS EXIT LIGHT AT WEST DOOR AS PER PLAN AND EAST POUR 3) WHERE IS DISCONNECTING MEANS FOR INSTA HOT 4) FINISH INSTALLING FIRE ALARM EQUIPMENT PER 760 |