Permit: T05CM02378

Parcel: 13417338A


Addresses:

606 S CYNTHIA AV


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T05CM02378

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
01/19/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
01/09/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) WATER TEST UNDERGROUND THRU BLDG TO 2-WAY CLEANOUT OK
2) NEED TO VIEW PIPE WRAPS PRIOR TO CONCRETE AND HCS CONNECTION
01/03/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE COMPLETE DWV SYSTEM, 10 ONE TYPE OF MATERIAL
2. PROVIDE LONG RADIUS DRAINAGE FITTINGS WHERE REQUIRED.
3. HAVE TEST IN PLACE AT TIME OF INSPECTION
4. PROVIDE RED LINE OF YOUR INSTALLATION AT TIME OF REINSPECTION
5. HAVE PIPING SHADED WITH GOOD MATERIAL.