Permit: T05CM02376

Parcel: 141013670

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM02376

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/02/2005 FRAMING Approved IVRS - Inspection :*
09/29/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXTEND SHEAR OUT TO H.D. REMOVE STUD SHEATHING TO BE CONTINOUS-INSUFFICIENT NAILS
2) BANG PLATES PEX AT WALLS 2ND FLOOR BATH BOTTOM PLATE
3) BANG PLATES THROUGHOUT
4) BACKING AT TUB 2ND FLOOR
09/27/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BLKS TOP OF SW1 IN LIVING ROOM AT TOP PL
2) EXTEND SHEAR OUT TO H.D. REMOVE STUD SHEATHING TO BE CONTINOUS
3) PEX TO CLOSE TO LIGHT CANS
4) BANG PLATE PEX AT WALLS
5) A.B.'S AT 32" ON CENTER BATH WALL #3 SHEAR
6) BANG PLATES THRU OUT
7) BACKING AT TUB 2ND FLOOR