Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 02/07/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL PENETRATIONS IN GARAGE WALLS |
|
| 02/06/2006 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED POSITIVE PITCH ON VENT PIPE ON FURNACE 2) CONNECT GAS TO FURNACE |
|
| 01/31/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CIRCUIT 13 NOT LABELED 2) CIRCUIT 13 14 GAGE WIRE 20 AMP BREAKER NOT ALLOWED 3) FURNACE NOT INSTALLED PER INSTALLATION MANUAL 4) NO FURNACE INSTALLATION MANUAL AFFIXED NEAR FURNACE |