Inspection History Details
Inspection Status: Partial Approval
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/01/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PENDING MECH 2) APPROVED TO INSULATE 3) BROKEN WINDOW IN ?.R. 4) FRESH AIR INTAKE REQUIRES 10' MINIMUM CLEARANCE TO FURNACE EXHAUST |
|
| 12/01/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 11/23/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE STUCCO MESH NAILING 6" ON CENTER-MUST HIT STUDS 2) REPLACE BLOCKING AT WATER HEATER 3) 1" CLEARANCE TO COMBUSTIBLES AROUND B-VENT 4) WIRES RESTING ON B-VENT 5) SEAL 2ND FLOOR PENETRATIONS 6) PROTECT WIRES FROM GANG PLATE ON FLOOR TRUSS OVER KITCHEN 7) OUTLET BY CLEANOUT IN KITCHEN TO BE ON SMALL APPLIANCE 8) TIGHTEN AB'S THROUGHOUT 9) STOPPED INSPECTION-TOO MANY ITEMS |