Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 11/04/2005 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER JEANNE |
|
| 11/03/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 7/SD3 REQUIRED AT 64" ON CENTER EAST WALL 2) REAR SHEAR MISSED STUD AT CHANNEL 3) DBL STUDS REQUIRED UNDER 3 1/8 X 9 GLB 4) ONE TRUSS NOT NAILED-UNDER DORMER |