Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 01/10/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BEDROOM SMOKE DETECTORS MUST BE ON ARC FAULT PROTECTED CIRCUIT 2) OUTSIDE HOSE BIBS REQUIRE ANTI-SIPHON VALVES 3) A/C NOT LEVEL 4) STOOP NOT IN-MUST BE 36" 5) POWER ROOM TOILET MUST BE 15" FROM CENTER LINE TO WALL 6) CAULK HALL TOILET TO FLOOR 7) ATTIC ACCESS BLOCKED BY DUCT 8) FURNACE SPARK SHIELD NOT PER PAGE ? INSTALLATION MANUAL 9) B-VENT CANNOT ENTER FURNACE CABINET PAGE 32 OF MANUAL |