Permit: T05CM02371

Parcel: 140376560


Addresses:

6849 S HARRIER LP

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/21/2005 FRAMING Approved IVRS - Inspection :*
11/17/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 2, 3, 4 AQND 8 FROM 11/14/05 NOT DONE
2) SOUTH SILL P-1 NOT NAILED
3) SUPPORT DWV 90 AT ROOF PENETRATIONS
4) WIRES MUST TERMINATE IN BOXES
5) ATTIC ELECTRIC NOT DONE
6) LIVING ROOM MISISNG NOTE "C" ANCHOR BOLTS
7) NO GAS TEST
11/14/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) INSPECTED HOUSE USING 2015 PLAN WITH NO P-U2 M02 B 1 D NUMBER AND 14 PAGES FROM S-1 THRU SD-4 WITH NO CITY OF TUCSON APPROVAL STAMP AND NO STAMP FROM A-4 PLAN CHECK AGENCY AT DIRECTION OF HECTOR LEYVA
2) GARAGE P-2 SHEAR WALL NOT ANCHORED PER NOTE C PAGE S-1
3) MASTER BATH TOILET NOT VENTED ABOVE CENTER LINE OF DRAIN
4) RED HEAD ANCHOR BOLTS LOOSE
5) RETRO FIT ANCHOR BOLTS AT PLATE SPLICES NOT INSTALLED PER JORDAN ENGINEERING INSPECTION LETTER
6) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF STUD SURFACES
7) POST TENSION SLAB CUT FOR PLUMBING REPAIR BY PANTRY. PROVIDE CITY APPROVED ENGINEERS REPAIR
8) MAXIMUM ALLOWED STAIR RISE IS 7 3/4" PRESENTLY 8"
9) MAXIMUM ALLOWED STAIR RISER DIFFERANCE 3/8" PRESENTLY 3/8" PRESENTLY 7 1/4"-8"
10) STOPPED INSPECTION-TO MANY ITEMS