Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 11/03/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 2 AND 5 FROM 11/2/05 NOT DONE |
|
| 11/02/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND CONDUTORS OVER TORQUED IN PANEL. REPAIR WIRES AND RETORQUE 2) A/C DISCONNECT CANNOT BE BEHIND CONDENSOR-SECURE WHIP 3) SEAL DRYWALL HOLE IN GARAGE BY TRANSFORMER 4) PARTIAL BEAR BULB LIGHT FIXTURE NOT ALLOWED IN STAIR CLOSET 5) PROVIDE FURNACE INSTALLATION MANUAL PER IRC 106.1.2 |