Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2005 | PLUMBING - INTERMEDIATE | Approved | 3" VTR IS OK IVRS - Inspection :* | |
| 09/21/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ONLY 24 FIXTURE UNITS MAYBE RUN ON A 2" VENT 2) THE CROSS SECTIONAL AREA OF THE VENT THRU ROOF MUST EQUAL THE REQUIRED BLDG SEWER 3) RE-TEST THE SYSTEM 4) OVERHEAD WATER DISTRIBUTION IS OK |
|
| 09/15/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) GREASE INTERCEPTOR INSTALLATION IS OK 2) OK TO BACKFILL TRENCH |
|
| 08/19/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) TRAP PRIMERS/UNDERGROUND WATER SUPPLIES BLOCKOUTS AND CLOSET WRAPS OK 2) OK TO CONCRETE |