Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05CM02364

Parcel: 121016460


Addresses:

1951 N WILMOT RD 03


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T05CM02364

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/09/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL C OF O
12/08/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) DUCT SMOKE DETECTOR NOT SHUTTING DOWN A/C UNIT
2) OK FOR TEMP C OF O
12/07/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) EXTEND EXHAUST DISCHARGE 2' ABOVE FRESH AIR INTAKE
2) PERMANENTLY IDENTIFY EQUIPMENT ON ROOF
3) FINISH FUSING DISCONNECTS
4) PROVIDE BUSHINGS IN KNOCKOUT HOLES IN A/C UNITS
5) NEED TO TEST DUCT SMOKE DETECTOR AC-3
12/05/2005 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*