Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T05CM02364

Parcel: 121016460


Addresses:

1951 N WILMOT RD 03

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/09/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL C OF O
12/08/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) DUCT SMOKE DETECTOR NOT SHUTTING DOWN A/C UNIT
2) OK FOR TEMP C OF O
12/07/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) EXTEND EXHAUST DISCHARGE 2' ABOVE FRESH AIR INTAKE
2) PERMANENTLY IDENTIFY EQUIPMENT ON ROOF
3) FINISH FUSING DISCONNECTS
4) PROVIDE BUSHINGS IN KNOCKOUT HOLES IN A/C UNITS
5) NEED TO TEST DUCT SMOKE DETECTOR AC-3
12/05/2005 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*