Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05CM02364
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL C OF O |
|
12/08/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) DUCT SMOKE DETECTOR NOT SHUTTING DOWN A/C UNIT 2) OK FOR TEMP C OF O |
|
12/07/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) EXTEND EXHAUST DISCHARGE 2' ABOVE FRESH AIR INTAKE 2) PERMANENTLY IDENTIFY EQUIPMENT ON ROOF 3) FINISH FUSING DISCONNECTS 4) PROVIDE BUSHINGS IN KNOCKOUT HOLES IN A/C UNITS 5) NEED TO TEST DUCT SMOKE DETECTOR AC-3 |
|
12/05/2005 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |