Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*OK FINAL | |
| 12/08/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20 2. CORD NOT ALLOWED FOR PERMANENT WIRING METHOD OR ABOVE CEILING. 3. VOV CABLEING TO BE SUPPORTED AT CEILING GRID 4. PLEASE LABEL PANELS ON OUTSIDE OF COVER 5. EXHAUST FAN LAB NOT WORKING 6. CORRECTLY IDENTIFY GROUNDED CONDUCTOR AND UNGROUNDED CONDUCTOR 7. PLEASE LABEL DISCONNECTS 8. RECEPTACLE TO BE WEATHERPROOF WHETHER OR NOT PLUGGED IN 406.8 9. TIGHTEN LOOSE FITTINGS 10. MAINTAIN WORKING CLEARANCE IN FRONT OF A/C DISCONNECT |
|
| 12/05/2005 | ELECTRIC - FINAL | Cancelled | ||
| 12/05/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |