Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T05CM02361
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/14/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1) 12 PSI AIR TEST FROM METER (THRU BLDG 1 1/2") TO BOOSTER HEATER (3/4") AND 1 1/4 TO COMB OVEN OK 2) PROVIDE SAFETY CABLES TO ALL GAS APPLIANCES ON WHEELS 3) COMPLETE PIPING TO BOOSTER HEATER AT DISHWASHER AT LATER DATE TO BE VIEWED BY INSPECTOR PRIOR TO USE. PROVIDE PLUG AT SHUT OFF VALVE FOR BOOSTER HEATER PRIOR TO ENERGIZING GAS PIPING |
|
09/09/2005 | PLUMBING - GAS PRESSURE TEST | Cancelled | CANCELLED PER ROBBIE OF LPS CONTRACTING #602-388-5567 | |
09/09/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
09/07/2005 | PLUMBING - GAS PRESSURE TEST | Cancelled | ||
09/07/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
09/06/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
08/30/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
08/29/2005 | PLUMBING - GAS PRESSURE TEST | Cancelled | ||
08/29/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
08/26/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) INSTALL GAS PIPING PER YOUR GAS ISOMETRIC DRAWING. DO NOT HOOK UP THERMALIZER TO EXISTING. DO NOT USE THIS EQUIPMENT UNTIL APPROVAL IS GIVEN. PROVIDE RIDGID PIPE NIPPLE OUT OF APPLIANCE HOUSING. SECURE GAS PIPING AT THERMALIZER |
|
08/18/2005 | PLUMBING - GAS PRESSURE TEST | Cancelled | CANCELLED PER ROBBIE SUPERINTENDENT #602-388-5567 | |
08/18/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
08/16/2005 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 1) 14 PSI TEST FROM STUB THRU WALL ON 1 1/2 OVER TO 3/4' DISHWASHER, AND UP TO 1 1/4 ANSUL VALVE (PARTIAL APPR) NEED HANGER AND SUPPORTS AT CORRECT INTERVALS THROUGHOUT CEILING SPACE. WILL NEED TEST ON SYSTEM TO METER AND THRU ANSUL VALVE TO APPLIANCE |
|
08/15/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO VIEW PIPING IN CEILING FOR CORRECT SUPPORTS, ANSUL VALVE LOCATION, CORRECT SIZING IN CEILING SPACE 2) YOU HAVE MOVED BACK IN DELI AREA, DRAINS FROM CASES ARE NOT APPROVED AND HAVE NOT BEEN INSPECTED THERE IS OVERHEAD WORK TO BE COMPLETED IN THIS AREA ALSO, VENTS FROM FLOOR SINKS ARE NOT COMPLETED AND TERMINATIONS 2) DRAINAGE FROM FOOD PREP CASES IS NOT APPROVED AND NOT DRAINING AT THIS TIME. CONTRACTOR TO PAY REFEE AND STOP USE OF THESE FOOD CASES IMMEDIATELY |