Permit: T05CM02361

Parcel: 13338005E


Addresses:

10380 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T05CM02361

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
09/14/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) 12 PSI AIR TEST FROM METER (THRU BLDG 1 1/2") TO BOOSTER HEATER (3/4") AND 1 1/4 TO COMB OVEN OK
2) PROVIDE SAFETY CABLES TO ALL GAS APPLIANCES ON WHEELS
3) COMPLETE PIPING TO BOOSTER HEATER AT DISHWASHER AT LATER DATE TO BE VIEWED BY INSPECTOR PRIOR TO USE. PROVIDE PLUG AT SHUT OFF VALVE FOR BOOSTER HEATER PRIOR TO ENERGIZING GAS PIPING
09/09/2005 PLUMBING - GAS PRESSURE TEST Cancelled CANCELLED PER ROBBIE OF LPS CONTRACTING #602-388-5567
09/09/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
09/07/2005 PLUMBING - GAS PRESSURE TEST Cancelled
09/07/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
09/06/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
08/30/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
08/29/2005 PLUMBING - GAS PRESSURE TEST Cancelled
08/29/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
08/26/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) INSTALL GAS PIPING PER YOUR GAS ISOMETRIC DRAWING. DO NOT HOOK UP THERMALIZER TO EXISTING. DO NOT USE THIS EQUIPMENT UNTIL APPROVAL IS GIVEN. PROVIDE RIDGID PIPE NIPPLE OUT OF APPLIANCE HOUSING. SECURE GAS PIPING AT THERMALIZER
08/18/2005 PLUMBING - GAS PRESSURE TEST Cancelled CANCELLED PER ROBBIE SUPERINTENDENT #602-388-5567
08/18/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
08/16/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) 14 PSI TEST FROM STUB THRU WALL ON 1 1/2 OVER TO 3/4' DISHWASHER, AND UP TO 1 1/4 ANSUL VALVE (PARTIAL APPR) NEED HANGER AND SUPPORTS AT CORRECT INTERVALS THROUGHOUT CEILING SPACE. WILL NEED TEST ON SYSTEM TO METER AND THRU ANSUL VALVE TO APPLIANCE
08/15/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO VIEW PIPING IN CEILING FOR CORRECT SUPPORTS, ANSUL VALVE LOCATION, CORRECT SIZING IN CEILING SPACE
2) YOU HAVE MOVED BACK IN DELI AREA, DRAINS FROM CASES ARE NOT APPROVED AND HAVE NOT BEEN INSPECTED THERE IS OVERHEAD WORK TO BE COMPLETED IN THIS AREA ALSO, VENTS FROM FLOOR SINKS ARE NOT COMPLETED AND TERMINATIONS
2) DRAINAGE FROM FOOD PREP CASES IS NOT APPROVED AND NOT DRAINING AT THIS TIME. CONTRACTOR TO PAY REFEE AND STOP USE OF THESE FOOD CASES IMMEDIATELY