Permit: T05CM02361

Parcel: 13338005E


Addresses:

10380 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T05CM02361

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
09/16/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
INSTALLATION OF 3" TRENCH DRAIN IN BAKONG? OK
09/09/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 1/2" GREASE WASTE FOR PA-134 WATER TEST OK
2) 2" FLOOR SINK DRAIN AND 2" VENT FOR DAIRY OK
3) NEED TO VIEW VENT CONNECTION TO EXISTING 3" VENT
4) 3" FLOOR SINK AND VENT FOR SOUTH PRODUCE WATER TEST OK
5) ONLY NEED TO INSPECT TRENCH DRAIN IN BAKERY FOR COMPLETION OF ROUGH SOIL INSPECTION
09/07/2005 PLUMBING - ROUGH, SOIL Cancelled CANCELLED PER ROBBIE OF LPS CONTRACTING #602-388-5567
09/07/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
09/06/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 2" GREASE WASTE FOR FLOOR SINK IN DELI AREA IS FLAT, 2" PIPE REQUIRES MINIMUM 1/4" PER FOOT FALL, SHADED PROPERLY AND NO DEBRIS IN DITCH
2) ADDITION OF 3" FOR 2" FLOOR SINK NORTH LOCATION OF PRODUCE WATER TEST OK
3) ADDITION OF 3" FOR 2" FLOOR SINK CENTER LOCATION OF PRODUCE WATER TEST OK AND H20 1/2" PIPING LOOPED FOR ? OK
08/30/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) NO THREADED ABS FITTING TO BE IN UN-ACCESSIBLE LOCATION EVEN FOR TEST. NEED PROOF OF TIE IN TO GREASE WASTE IN DELI AREA FOR 3-COMP SINK
2) 4" COMBINATION WASTE AND VENT FOR BEVERAGE CASE PER REVISED PLAN DATE 8/9/05. WATER TEST TO 10' AFF OK PENDING CITY APPROVAL OF THIS PLAN
08/29/2005 PLUMBING - ROUGH, SOIL Cancelled CANCELLED PER ROBBIE CONTRACTOR #602-388-5567
08/29/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
08/26/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) WATER TEST 3" FLOOR SINK FOR 2 COMP SEAFOOD PREP SINK AS PER APPROVED PLAN OK
08/25/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMBINATION WASTE AND VENT SYSTEM ADDED FOR BEVERAGE CASES IS A NEW ADDITION TO THIS PLAN AND WILL REQUIRE CITY APPROVED REVISED PLANS FOR DRAINAGE. PLUMBER CHECK MAXIMUM TAIL PIECE DISTANCE FOR DRAINAGE DEVICES
08/24/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) FLOOR DRAIN ON GREASE WASTE SYSTEM FOR SEAFOOD PREP SINK WATER TEST OK-RED LINE ON SITE
08/23/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) CAP ON DEMO FLOOR SINK UNDER SLAB IN FLORAL AREA OK
2) 3" GREASE WASTE FOR SEAFOOD SINK REQUIRES RED LINE ON SITE AT TIME OF INSPECTION
3) ALL VENTS AND DRAINS TO BE KEPT CAPPED AT ALL TIMES TO PREVENT SEWER GAS FROM ENTERING BLDG STRUCTURE
08/22/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) REROUTE OF (2) FLOOR SINKS ON COMBINATION WASTE AND VENT SYSTEM IN MOAT/SOA FOOD PREP OK WASTER TEST OK
2) ADDITION OF LAV IN MOAT/SOAFOOD PREP WATER TEST OK
08/16/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 2" LOOP VENT AND DRAIN FOR SINK IN FLORAL ISLAND WATER TEST OK
2) TO 10' ABOVE FINISH FLOOR. H20 PIPING SAME AREA OK. 1/2" HELIUM LINE BELOW GRADE ONLY OK
08/15/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL PER YOUR DETAIL PAGE P1.7 #5
08/12/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
NO TEST ON PIPING AT THIS TIME, TEST BALL LET GO.
08/10/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) RELOCATION OF FS-2 IN DELI AREA WATER TEST OK
2) NEED TO SEE 2" GREASE WASTE IN DELI AREA FOR ROUGH SOIL ALL OTHER DELI ROUGH SOIL INSPECTION
08/09/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PIPING IS TO BE DIRECTLY EMBEDDED IN CONCRETE
2) YOUR FLOOR DRAIN PIPING IS BACK PITCHED
3) YOU DON'T HAVE APPROVAL FOR SODE DISPENSOR USE, INFORMING MANAGER THIS IS NOT TO BE USED UNTIL APPROVAL GIVEN
4) CAP OFF ALL VENT PIPING THAT IS NOT TERMINATED THRU ROOF IMEEDIATELY IF IT IS CONNECTED TO SANITARY SYSTEM. THIS IS AN UN-SANITARY CONDITION
5) I LEFT MESSAGES AT BOTH PHONE NUMBERS, YOU HAVE MY PHONE NUMBER CONTACT ME IMMEDIATELY. ITEM #3 AND #4 NEED TO BE ADDRESSED IMMEDIATELY
6) YOU ARE DUMPING CONDENSATE INTO THE DIRT AT THE MEAT DISPLAY AREA THIS NEEDS IMMEDIATE ATTENTION ALSO
08/08/2005 PLUMBING - ROUGH, SOIL Cancelled CANCELLED PER ROBBIE OF LPS CONTRACTING (602) 388-5567
08/08/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
08/04/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST UNDERGROUND FOR MOP SINK AND FLORAL SINK IN FLORAL AREA (OK) FS-2 SHOWN AS NOW IS NOT APPROVED BECAUSE EXISTING IS IN A USABLE LOCATION.
CAP FOR BWC AT WEST ENTRY DOOR DRAIN IS OK THIS IS RELOCATED TO DBLI WALL. ROD LINE ON SITE REVISED CITY APPROVED PLAN TO FOLLOW.
1. WILL NEED TO SEE PERM CAP ON DEMO IN FLORAL AREA FOR SINK & MOP SINK.
2. NEED REVISION FOR AIR ADMITTANCE VALVE ON VENT AT FLORAL SINK. COVER AT OWN RISK OR INSTALL VENT PER PLAN.
3. PROVIDE DETAIL FOR TRENCH FOR HELIUM PIPING.
08/03/2005 PLUMBING - ROUGH, SOIL Cancelled
08/03/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
08/02/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) WATER TEST SANDWICH AREA ONLY ADDITION OF (2) FLOOR SINKS (1) HAND SINK AND RED LINE OF ADDITIONAL ELECTRIC WATER FOUNTAIN. OK TO 10' ABOVE FINISH FLOOR. REVISED CITY APPROVED PLAN TO SHOW ADDITION OF EWF. COVER AT OWN RISK
07/28/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
CALLED YOU ROBBIE ON MY WAY HERE NO PERSONNEL ON SITE NO ACCESS TO PLANS & PERMIT
07/26/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) CAPING OF DELETED PIPING FOR DAIRY CASE AREA PER RED LINE ON SITE OK-PENDING CITY APPROVED REVISION OF ALL DELETED WORK ON THIS SITE. INSTALLATION OF (1) FLOOR SINK AT GRAB AND GO WATER. WATER TEST TO 10' ABOVE FINISH FLOOR PER RED LINE DRAWING ON SITE OK. PENDING CITY APPROVAL OF REVISED PLAN AT FUTURE DATE. WATER TEST OF (1) FLOOR SINK IN NEW BEVERAGE AREA TO 10' ABOVE FINISH FLOOR OK-PENDING ADDITION OF THIS FIXTURE TO REVISED CITY APPROVED PLAN RED LINE ON SITE
07/25/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) SEE NOTE #2 FROM 7/21/05. PLEASE HAVE SOMEONE PRESENT OR LEAVE A CONTACT PHONE NUMBER SO ACCESS WILL BE MADE AT TIME OF INSPECTION
07/21/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WATER TEST REQUIRES 10' HEAD
2) VENTS PIPING BELOW FLOOD RIM OF FIXTURE TO BE LONG RADIUS DRAINAGE FITTINGS
3) PROVIDE CORRECT FACE ON PIPING
4) SHADE PIPING CORRECTLY TO PROVIDE FIRM BED FOR PIPING
5) PLAN IS APPROVED IN ERROR-HAND SINK REQUIRES SANITARY DRAIN CANNOT GO INDIRECT WASTE. HAND SINK SHOULD NOT BE ON COMBINATION WASTE AND VENT SYSTEM. EACH DIRECT CONNECTION TO POTABLE H20 SYSTEM THAT MIXES ANOTHER SUBSTANCE TO IT REQUIRES SEPERATE BACKFLOW PROTECTION. EACH APPLIANCE REQUIRES SEPERATE BACKFLOW PROTECTION I.E. ICE MACHINES, ETC..
6) INSTALL WASTE AND VENT PER MP1.2 SECTION 1.6 A. THIS IS NOT A COMPLETE LIST
07/19/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*