Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/25/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL GROUND CONDUCTOR FOR A/C UNIT 2. CHASE NIPPLE NOT AN APPROVED FITTING TO BOX 3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR 4. SUPPORT SEAL TITE UP OFF THE ROOF. 5. CORRECTLY INSTALL SEALTITE FITTINGS 6. VEGETATION STILL GROWING IN FRONT OF SERVICE |
|
| 08/23/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH ROOF 2. MAINTAIN CLEARANCE IN FRONT OF SERVICE 3. LABEL MAIN'S OK UNIT INTERIORS |