Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/22/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
03/21/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. UNIT A REQUIRES CORRECT RATED FLEX FOR BTU REQUIREMENTS OF FURNACE NO LONGER THAN 3'
2. PROVIDE COCKHOLE COVER AT KITCHEN SINK.
3. PROVIDE CORRECT HIGH LOOP SUPPORT OF DISHWASHER HOSE.
03/20/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
03/16/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
#A NOT READY
UNITS B,C & D ARE OK FOR FINAL
03/15/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
FOLLOWING CORRECTIONS NEEDED
UNIT C
1. SECURE 5" VENT CONNECTOR TO VENT
2. DRIP ON COLD ANGLE STP
3. HANDLE ON TUB IS UPSIDE DOWN
UNIT D
1. REMOVE DIP (TRAP) FROM DW HOSE BETWEEN HIGH POINT AND CONNECTION TO DISPOSER.
2. LEAK UNDER KIT SINK
3. APPROVED LISTED CLEAN OUT PLUG REQUIRED TO RECEIVE SCREW FROM COVER PLATE.