Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/14/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CLEAN TERMINALS OF FOREIGN MATERIAL 11.12 (SUB PANELS) 2. NEED MECHANIC DUCT INSTALLED BY SUB PANELS TO VERIFY CLEARANCES AS DISCUSSED 3. UNIT "B" HAS NO POWER AT THIS TIME. |
|
| 03/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE #110.26 2) PLEASE LABEL METERS AND ADDRESS THE SERVICE 3) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314320 TO BE FLUSH AT COMBUSTIBLES 4) PROPERLY GROUND FIXTURES 5) SECURE BOX IN WALL 6) OK ROOF |