Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL 2) FLUE PIPE TO BE INSTALLED AS DISCUSSED |
|
| 09/13/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20 ALSO FLUSH ON COMBUSTIBLES 2) LABEL CIRCUIT DIRECTORY FOR BREAKERS TO BE PERMANENT 110.22 3) GROUND LIGHT FIXTURE TO CIRCUIT 4) DUCT WORK BLOCKING JUNCTION BOX ACCESS 5) MAINTAIN CLEARANCES AS DISCUSSED WITH FLUE PIPES 6) TIGHTEN LOOSE CARFLEX FITTINGS AND SUPPORT CARFLEX 7) CORRECTLY IDENTIFY UNDERGROUND CONDUCTORS 8) LABEL A/C DISCONNECTS 9) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE 10) LABEL SERVICE |