Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 10/21/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO SERVICE UPGRADE TO 200 AMPS ON PERMIT NEED TO ADD TO PERMIT 2) EXPOSE UFER GROUND RODS 3) GROUND METAL BOXES 4) EXPOSE ROMEX WIRE RUNS 5) WIRES MUST BE MADE UP FOR INSPECTION 6) FRAMING NOT PER PLAN AT EXTERIOR WALLS CALLS FOR 2 X 6 AND R30 NOT R13 7) INSPECTION 1005 AND 1015 SHOULD BE PARTIAL APPROVAL PENDING FRONT PATIO 8) EXTERIOR S/B STUCCO AS PER PLAN, SIDING HAS BEEN INSTALLED 9) NEED SMOKE DETECTOR IN BEDROOM AND OUTSIDE BEDROOM |