| 08/16/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 08/15/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL 250.24 2) ONLY ONE NEUTRAL PER TERMINAL 3) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 |