Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM02311
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/07/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/25/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DSB-1-EE28 600 AMP J-BOX OK, J519 400 AMP J-BOX OK, NN2 400 AMP J-BOX OK 2) DSB-2 J-BOX W-28 TO PNL B-44 OK 3) DSB-1 EE-28 BREAKER OK, JJ19 BREAKERS OK, NN-2 BREAKERS OK, EE-37, V-3 BREAKER OK, PNL EE-37 OK AND J-BOX BUSS V3 400 AMP OK 4) 922 PRESS NO LISTING-APPROVAL SUBJECT TO EE VERIFICATION DISCONNECT OK 5) 2039 PRESS NO LISTING-APPROVAL SUBJECT TO EE VERIFICATION DISCONNECT OK |
|
08/16/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | 1) BUS W-28 TERMINATE AND ROPE J-BOX 2) V-44 NEEDS J-BOX TO HAVE SPLICED CONDUCTORS |
|
08/15/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | 1) OK TO COVER WALLS FOR BATHROOM | |
08/05/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ARPAC RETAIL PACK LINE TS-37NF SN 6447 2) ARPAC OVEN VT 122272 SN 6643 3) REVIEWED ENGINEERS REVIEW (UNLISTED) OK TO USE |
|
08/03/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) #1 MULTI POINT WELDER #3?9 2) CHICAGO BREAK PRESSURE #1280 3) MINISTER PRESSURE #3911 4) BROWN BOGGS PRESSURE #2314-ALL ABOVE VERIFIED THRU ENG-LETTER ON FILE-OK TO USE 2) BUS DUCT SECTION Q-30 DISCONNECT TO END OF BUS DUCT OK |
|
07/27/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | 1) MINISTER PRESSURE #2459 S/N 7O-4 15564 MODEL #70-4 GAP 2) SUTHERLAND PRESSURE 4096 S/N 200305009 MODEL MARK 220 3) ? 105 PRESSURE #088 MODEL 45 TON OB1 4) MINISTER PRESSURE #592-ALL EQUPMENT ABOVE REVIEWED BY EE ? MATHEWS PE-OK FOR USES/BUS J-BOX FOR X-15 OK (BUS DUCT) 400A, BUS J-BOX FOR G-30 OK (BUS DUCTS) 800A, BUS J-BOX FOR G-23 OK (BUS DUCT) 400A 5) OVER CURRENT PROTECTION ON BUST DUCT FOR ITEMS 1-4 OK 6) CONTRACTOR TO PROVIDE APPROVED REVISIONS FOR FINAL APPROVED FOR OPERATION ON EQUIP ITEMS 1-4 |
|
07/26/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SW GEAR SES #1 OK 2) 6-3" CONDUITS WITH 3-400 MCM PER AND NEUTRAL INCLUDING 250 MCM EQ GRD 3) DSB #1 4) 600 A CB 5) 1-4" 3-600 MCM AND #3 GRD TO J-BOX 6) J-BOX OK 7) BUS JUNCTION NEEDS TO BE ? PER INSTRUCTIONS 8) SES #4 GFI TEST WITNESS BY THIS INSPECTOR-APPROVED |
|
07/14/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SES 1: NEW 2000 AMP SW GEAR-PRMARY AND SCONDARY TERMINATIONSOK, BOTTOM CONDUIT TY-RAP CONDUCTORS AWAY FROM BUS NWT. 2) SES 2: TERMI9NATIONS PRIMARY OK. NEED GFI TEST AND LETTER OF TORQUE |
|
07/13/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) GFI TEST ON NEW 2000A-480 GEAR OK 2) GE ELECTRICAL DISTRIBUTION AND CONTROL TESTER FOR GFI TEST ON GE ? SW GEAR TURMS 2, 2000A, 480V, 3/0, AIC 65,000. TEST BY KELLY ELECTRIC (SHAUN MEEHAN). TEST ON SITE VIEWED BY RAY MAJUTA 7/13/05 2) SECONDARY SW GEAR-OK. DO NOT ENERGIZE EQMT 3) EQUIPMENT TO BE ENERGIZED MUST BE LISTED AND APPROIVED BY OSHA APPROVED TESTING LAB 4) REVISE PLANS-MUST BE APPROVED |
|
07/08/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1 PM NOT READY CONDUCTORS NOT INSTALLED |