Permit: T05CM02311

Parcel: 107070080

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/07/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/25/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DSB-1-EE28 600 AMP J-BOX OK, J519 400 AMP J-BOX OK, NN2 400 AMP J-BOX OK
2) DSB-2 J-BOX W-28 TO PNL B-44 OK
3) DSB-1 EE-28 BREAKER OK, JJ19 BREAKERS OK, NN-2 BREAKERS OK, EE-37, V-3 BREAKER OK, PNL EE-37 OK AND J-BOX BUSS V3 400 AMP OK
4) 922 PRESS NO LISTING-APPROVAL SUBJECT TO EE VERIFICATION DISCONNECT OK
5) 2039 PRESS NO LISTING-APPROVAL SUBJECT TO EE VERIFICATION DISCONNECT OK
08/16/2005 ELECTRIC - INTERMEDIATE Partial Approval 1) BUS W-28 TERMINATE AND ROPE J-BOX
2) V-44 NEEDS J-BOX TO HAVE SPLICED CONDUCTORS
08/15/2005 ELECTRIC - INTERMEDIATE Partial Approval 1) OK TO COVER WALLS FOR BATHROOM
08/05/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ARPAC RETAIL PACK LINE TS-37NF SN 6447
2) ARPAC OVEN VT 122272 SN 6643
3) REVIEWED ENGINEERS REVIEW (UNLISTED) OK TO USE
08/03/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) #1 MULTI POINT WELDER #3?9
2) CHICAGO BREAK PRESSURE #1280
3) MINISTER PRESSURE #3911
4) BROWN BOGGS PRESSURE #2314-ALL ABOVE VERIFIED THRU ENG-LETTER ON FILE-OK TO USE
2) BUS DUCT SECTION Q-30 DISCONNECT TO END OF BUS DUCT OK
07/27/2005 ELECTRIC - INTERMEDIATE Partial Approval 1) MINISTER PRESSURE #2459 S/N 7O-4 15564 MODEL #70-4 GAP
2) SUTHERLAND PRESSURE 4096 S/N 200305009 MODEL MARK 220
3) ? 105 PRESSURE #088 MODEL 45 TON OB1
4) MINISTER PRESSURE #592-ALL EQUPMENT ABOVE REVIEWED BY EE ? MATHEWS PE-OK FOR USES/BUS J-BOX FOR X-15 OK (BUS DUCT) 400A, BUS J-BOX FOR G-30 OK (BUS DUCTS) 800A, BUS J-BOX FOR G-23 OK (BUS DUCT) 400A
5) OVER CURRENT PROTECTION ON BUST DUCT FOR ITEMS 1-4 OK
6) CONTRACTOR TO PROVIDE APPROVED REVISIONS FOR FINAL APPROVED FOR OPERATION ON EQUIP ITEMS 1-4
07/26/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SW GEAR SES #1 OK
2) 6-3" CONDUITS WITH 3-400 MCM PER AND NEUTRAL INCLUDING 250 MCM EQ GRD
3) DSB #1
4) 600 A CB
5) 1-4" 3-600 MCM AND #3 GRD TO J-BOX
6) J-BOX OK
7) BUS JUNCTION NEEDS TO BE ? PER INSTRUCTIONS
8) SES #4 GFI TEST WITNESS BY THIS INSPECTOR-APPROVED
07/14/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SES 1: NEW 2000 AMP SW GEAR-PRMARY AND SCONDARY TERMINATIONSOK, BOTTOM CONDUIT TY-RAP CONDUCTORS AWAY FROM BUS NWT.
2) SES 2: TERMI9NATIONS PRIMARY OK. NEED GFI TEST AND LETTER OF TORQUE
07/13/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) GFI TEST ON NEW 2000A-480 GEAR OK
2) GE ELECTRICAL DISTRIBUTION AND CONTROL TESTER FOR GFI TEST ON GE ? SW GEAR TURMS 2, 2000A, 480V, 3/0, AIC 65,000. TEST BY KELLY ELECTRIC (SHAUN MEEHAN). TEST ON SITE VIEWED BY RAY MAJUTA 7/13/05
2) SECONDARY SW GEAR-OK. DO NOT ENERGIZE EQMT
3) EQUIPMENT TO BE ENERGIZED MUST BE LISTED AND APPROIVED BY OSHA APPROVED TESTING LAB
4) REVISE PLANS-MUST BE APPROVED
07/08/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999* 1 PM NOT READY CONDUCTORS NOT INSTALLED