Permit: T05CM02283

Parcel: 140383710

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
09/30/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
09/28/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAIL PROTECT PLUMBING AT 1 1/4" OF PLATE SURFACE KITCHEN
2) ONE ROOF PANEL NOT NAILED ON EDN AT 6" ON CENTER SOUTH END OF HOUSE
09/23/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 1, 3 AND 7 FROM 9/20/05 NOT DONE
2) MANY ROOF PANELS NOT NAILED
09/20/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) ENTRY DORMER BEARING WALLS CANNOT BEAR ON OSB ONLY. PROVIDE CIRY OF TUCSON APPROVED DETAIL FOR BEARING POINTS
2) TRUSS BRACING MISSING - SEE TRUSS DRAWINGS
3) PROVIDE CIRY APPROVED DETAIL FOR SHEAR WALL 5 TRANSFER TO TRUSSES
4) PORCH COLUMN NOT ANCHORED/CLIPPED PER PLAN
5) PORCH GLUE LAN BEAM NOT BEARING ON PORCH POST
6) HEADERS MUST BEAR ON TRIMMERS
7) NAIL PROTECT PLUMBING WITHIN 1 1/4 " OF PLATE SURFACES
8) TRUSSES NOT BEARING ON MID BEARING POINT
STOPPED INSP TOO MANY ITEMS