Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 09/20/2005 | FRAMING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio 1) STRIP WINDOWS NOT COMPLETE YOU MUST PAY A REINSPECTION FEE |
|
| 09/19/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* OK TO INSULATE 1) STAIR WINDER MUST BE A MINIMUM OF 6" ON NARROW END 2) INSTALL TWO ANCHOR BOLTS IN 2X4 PLATE BY PATIO DOOR NOTE: 56 PL 1.1 IRC 309.2 AND 702.3.5 |
|
| 09/15/2005 | FRAMING | Not ready for Inspection | COMPLETE NAILING LATH | |
| 09/15/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL PROTECT PLUMBING AT W/H 2) SEAL FLOOR PENETRATIONS II F.B 3) NO DWV WATER TEST 4) NAIL STAIR STRINGERS 5) STAIR WINDOW MUST BE 6" MINIMUM ON NARROW END 6) ELECTRIC OUTLET REQUIRED WITHIN 6 FOOT OF STAIR TOP RAIL 7) ANCHOR W/C FLOOR FLANGES 8) INSTALL A-B ON 2X4 PLATE BY PATIO DOOR 9) RE ROUTE FAN DUCT LAUNDRY |