Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 08/22/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF STUD SURFACE 2) REMOVE NAILS AND REPAIR ROUGH PLUMBING DAMAGED BY NAILS 3) RIBBON ABOVE P.3 SHEAR WALL NOT NAILED AT 3" OO 4) P-1 SHEAR MUST BE NAILED AT 7" D.C ENDS AND EDGES 5) CS 20 STRAPS TOO SHORT |
|
| 08/17/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF STUD SURFACES 2) REMOVE NAILS AND REPLACE ROUGH PLUMBING AT REAR OF HOUSE 3) LUS 24 HANGERS MISSING ENTRY 4) HEADERS MUST BEAR ON TRIMMERS 5) P-3 SHEAR AND RIBBON NOT NAILED AT 3" ON CENTER 6) SECOND FLOOR P-1 MUST BE 8' IN LENGTH 7) SECOND FLOOR WINDOW 5060 NOT PER PLAN 8) CS20 STRAPS DO NOT EXTEND TO FIRST FLOOR 9) ROOF SHEATHING NOT NAILED TO TRUSSES-TWO LOCATIONS |