Inspection History Details
Permit: T05CM02250
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2007 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :* | |
| 11/22/2006 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* | |
| 09/27/2006 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* - YOU HAVE BACKPITCH IN AT LEAST 2 AREAS. - YOUR SITE UTILITY PLAN DOES NOT HAVE PLUMBING PLANS EXAMINER STAMP. - YOUR FOUNDATIONS PLAN DOES AND IT CALL FOR A TWO WAY C/O TO BE INSTALLED, THIS IS REQUIRED BY CODE TO SERVE THE SECTION OF 4" BUILDING DRAIN, AS YOUR UPPER TERMINAL COS ARE ONLY 3". ALSO, CALL FOR BOTH ADDRESSES. |
|
| 09/19/2006 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOT ALL SITE SEWER IS EXISTING. PROVIDE SITE UTILITY PLAN SHOWING THAT TWO SEPARATE BUILDINGS W/DIFFERENT ADDRESSES TIE INTO A COMMON SEWER. A JOINT SEWER AGREEMENT IS ALSO NECESSARY. INSTALL EXTERIOR SEWER CLEANOUTS INSTALL TRACER WIRE |