Permit: T05CM02246

Parcel: 10825007D


Addresses:

2010 E RIVER RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/28/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL PLAQUE @ SERVICE - NEC 230.2E
2. MAX 30 AMP. BREAKER ON DRYER CKT - NEC 310, NEC 240.4
3. MAX 30 AMP BREAKER FOR AC'S - NEC 240.4
4. MAX 30 AMP BREAKER TO WATER HEATER - NEC 240.4
5. MAX 30 AMP BREAKER TO FURNACE - NEC 240.4
6. MULTI-WIRE BRANCH CKT TO TERMINATE ON SEPARATE PHASES.
7. FINISH WIRING ON ROOFTOP AND INSTALL PROPERLY SIZED FUSES.