Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM02246
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL PLAQUE @ SERVICE - NEC 230.2E 2. MAX 30 AMP. BREAKER ON DRYER CKT - NEC 310, NEC 240.4 3. MAX 30 AMP BREAKER FOR AC'S - NEC 240.4 4. MAX 30 AMP BREAKER TO WATER HEATER - NEC 240.4 5. MAX 30 AMP BREAKER TO FURNACE - NEC 240.4 6. MULTI-WIRE BRANCH CKT TO TERMINATE ON SEPARATE PHASES. 7. FINISH WIRING ON ROOFTOP AND INSTALL PROPERLY SIZED FUSES. |