Permit: T05CM02246

Parcel: 10825007D


Addresses:

2010 E RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05CM02246

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/27/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/30/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SUPPORT NM CABLES WITHIN 12" OF CANS
2. MISSING EXHAUST FANS

OK SOFFITS EXCEPT FANS 1ST FLOOR
11/21/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL COVER INTERIOR - ATTIC ACCESS AND AIR HANDLER LOCATIONS YET TO BE DETERMINED
GREAT JOB!
11/09/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FIRST FLOOR ELECTRICAL COVER
11/06/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CORRECTIONS IN PROGRESS --
TALK ABOUT ALL CORRECTIONS WITH RAMON
11/02/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) DO NOT CALL FOR INSPECTIONS BEFORE ELECTRICIANS ARE READY OR BEFORE CORRECTION HAVE BEEN COMPLETED OR FEE'S WILL BE CHARGED
11/01/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED CRIMP SLEEVES (PROPER TOOL) OR WIRE NUTS ON EQUIPMENT GROUNDS. NEC 110
2. IDENTIFY WHITE USED AS HOT - NEC 200.7
3. STAPLE ROMEX WITHIN 12" OF BOX -- NEC 334.30
4. INSTALL NAIL PLATES AS NEEDED -- NEC 300.4
5. HAVE OVERFILLED BOXES -- NEC 314.16 - 110.3
6. NEED RECEPTACLE WITHIN 6' OF BROKEN WALL LINE -
NEC 210.52
7. TERMINATE FEEDER RACEWAYS INTO PANELS
8. REMOVE MAIN BONDING SCREWS FROM SUB-PANELS
9. BATH RECEPTACLES NEED TO BE DEDICATED - NEC 210.11
10. KITCHEN COUNTER RECEPTACLES TO BE DEDICATED --
NEC 210.52
10/25/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER KITCHEN CEILING AREAS AND EXTERIOR SOFFIT AREAS ON LOWER LEVEL ONLY -- NO INTERIOR INSPECTION.