Permit: T05CM02246

Parcel: 10825007D


Addresses:

2010 E RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T05CM02246

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
07/24/2006 ELECTRIC - UFER Approved IVRS - Inspection :*
07/21/2006 ELECTRIC - UFER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED TO BOND TO REBAR WITH A CLAMP USED AS IT IS LISTED (A CLAMP LISTED FOR YOUR WIRE SIZE, NOT JUST SQUEEZED IN A SMALLER CLAMP) NEC 110.3