Permit: T05CM02244

Parcel: 129041150


Addresses:

1932 E 10TH ST

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
11/07/2005 ROOF NAILING Approved IVRS - Inspection :*
11/03/2005 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) AB THROUGHOUT
2) NAIL PROTECTION THROUGHOUT ELECTRIC AND PLUMBING
3) CONDUIT ABOVE SHOWER NOT CODE COMPLIANT
4) INSTALL EXHAUST FAN IN GARAGE
5) 1" CLEARANCE TO COMBUSTIBLES ON B-VENTS
6) TEST GAS LINE WITH APPROVED GAUGE
7) ROOF SHEATHING RUNNING WRONG DIRECTION
8) BLOCK HVAC BOOTS
9) BOND BAR BETWEEN NEUTRAL AND GROUND BUS TO BE REMOVED FOR SUB PANEL