Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/09/2005 | ELECTRIC - FINAL | Partial Approval | OK FOR TEMP C/O FOR TRAINING OF EMPLOYEES ONLY | |
| 11/08/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*OK ? TEMP C OF O FOR TRAINING OF EMPLOYESS ONLY SEAL WALKIN PENETRATION OF CONDUIT & IN CONDUIT, INSTALL PROTECTIVE LENSE @ FIXTURE |
|
| 11/08/2005 | ELECTRIC - FINAL | Not ready for Inspection | FINISH ITEMS #3,5 OF PREVIOUS INSPECTION | |
| 11/07/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 FINISH OFFICE SWITCH/EXTENDER RING-BOX BY BACK DOOR TIGHTEN LOOSE FITTING INSIDE WALK TO BOX SUPPORT VDV CABLEING UP OFF OF GRID 725.6 SEAL CONDUIT ( INSIDE) AT ENTRANCE TO BOX ( WALKING) AS PER 300.7 SUPPORT SEAL TITE ABOVE WALK IN BOX |