Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2005 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
| 10/27/2005 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :*IDENTIFY BONDING CONDUCTOR WITH GREEN TAPE BONDING JUMPER TO BE SIZED PER 250.102 & 250.66 FUSES ARE NEEDED LABEL DICONNECTS INSTALL FEEDER CONDUCTORS BOND CONDUCTOR NEEDED FOR METER ?? BUSHING FILL UNUSED OPENINGS DEVICES AND PLATES TO BE INSTALLED 8' AND BELOW |
|
| 10/26/2005 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* |