Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/03/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :*FINISH ITEMS # 4 & 5 OF PREVIOUS INSPECTION SEAK ENTRANCE TO WALK IN BOX AS PER 300.7 |
|
| 10/31/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :*BOXES IN COMBUSTIBLES TO BE FLUSH OR USE AN APPROVED EXTENDER RING DRYWALL SCREWS NOT ALLOWED FOR GROUNDING , CLEAN SURFACE UNDER GROUND BAR, FILL UNUSED OPENINGS-CONTROL CABINET SUPPORT RECESSED CANS,EM BOXES & BALLAST. ATTACH CANS TO GRID EXIT LIGHTING FINISH HOODS, BOX MAKE UP |
|
| 10/21/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*NORTH FRONT SOFFIT, EAST INTERIOR SOFFIT EAST EXTERIOR SOFFIT. |