Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05CM02240
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/14/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) ITEM #4035 NOT APPLICABLE PER PAPERWORK TURNED IN BY INSPECTOR C. WILLIAMS 2) BLOCK/CLAMP 3/4" PVC ON 4 FT. CENTERS 3) USE ROOF ADHESIVE BETWEEN BLOCKS AND ROOF SURFACE TO PROVIDE STABILITY 4) UNITS #10-24, 9-23, 8-22 AND 7-21 HAVE CONDEN TRAP IN EXTERNAL DRAIN LINE. ALL UNITS HAVE INTERNAL TRAPS. THESE TRAPS NEED TO BE REMOVED TO ELIMINATE VAPOR ? 5) CANNOT TERMINATE CONDENSATE DRAINAGE ON SIDEWALKS 6) UNIT #7 LOOSE HIGH VOLTAGE AT SWITCH 7) LIFT ELECTRIC FLEX LINES UP OFF OF ROOF SURFACE 8) UNITS #1 AND #2 ?? |