Inspection History: MECHANICAL - FINAL

Permit Number - T05CM02240

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/30/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/14/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) ITEM #4035 NOT APPLICABLE PER PAPERWORK TURNED IN BY INSPECTOR C. WILLIAMS
2) BLOCK/CLAMP 3/4" PVC ON 4 FT. CENTERS
3) USE ROOF ADHESIVE BETWEEN BLOCKS AND ROOF SURFACE TO PROVIDE STABILITY
4) UNITS #10-24, 9-23, 8-22 AND 7-21 HAVE CONDEN TRAP IN EXTERNAL DRAIN LINE. ALL UNITS HAVE INTERNAL TRAPS. THESE TRAPS NEED TO BE REMOVED TO ELIMINATE VAPOR ?
5) CANNOT TERMINATE CONDENSATE DRAINAGE ON SIDEWALKS
6) UNIT #7 LOOSE HIGH VOLTAGE AT SWITCH
7) LIFT ELECTRIC FLEX LINES UP OFF OF ROOF SURFACE
8) UNITS #1 AND #2 ??