Permit: T05CM02226

Parcel: 106031100


Addresses:

104 W NAVAJO RD #01


Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Permit Number - T05CM02226

Inspection Description - PLUMBING - SEWER HCS CONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
09/21/2006 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
CORRECTIONS MADE OK
OK TO COVER
09/20/2006 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
1. STILL BACKPITCHED SECTIONS.
2. REMOVE REPAIR COUPLINGS (FURNACE) AND USED SOLVENT WELD COUPLINGS.
09/18/2006 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
CORRECT BACK PITCHED SECTIONS AND RECALL 03055
FOR REINSPECTION OF EXPOSED ABS SEWER CONNECTING ALL FOUR BLDGS.
09/14/2006 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
1. PLAN CALLS FOR PVC INSTALLED IS ABS
2. NOT INSTALLED PER PLAN WILL REQUIRE ACCURATE "REDLINES"
3. TRACER WIRE TO BE CONTINUOUS OR USE WATER TIGHT WIRE NUTS AT CONNECTIONS.
4. OK TO COVER HCS CONNECTION UP TO CORNER OF BLDGS.