Permit: T05CM02226

Parcel: 106031100


Addresses:

104 W NAVAJO RD #01


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM02226

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/18/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/17/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
STILL NEED TO FINISH PREVIOUS CORRECTIONS
1, 4, 5, 7 FROM PREVIOUS LIST ON ROOF, SEAL UNUSED RACEWAYS.
04/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IDENTIFY "SERVICE DISCONNECTS" AS SUCH -- NEC 230.70B
2. SECURE GROUNDING ELECTRODE CONDUCTORS TO STRUCTURE -- NEC 110
3. CORD FOR HOOD NEEDS CONNECTOR -- NEC 400.10, 400.14
4. INSTALL APPLIANCES (RANGE)
5. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED -- NEC 408.4
(MICRO, REFRY?)
6. PROVIDE DISCONNECTING MEANS FOR WATER HEATER - NEC 422.31B
7. HAVE SEVERAL LOOSE RECEPTACLES -- NEC 406.4
8. ALL UNITS TO BE UNLOCKED FOR INSPECTION AND PROVIDE ROOF ACCESS (LADDER). CHECK ALL OTHER BUILDINGS FOR THESE CORRECTIONS BEFORE YOU CALL THEM IN

PLEASE, CALL EACH BUILDING IN AT A TIME, AS IT IS FINISHED NOT ALL AT ONCE.