Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM02226
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/17/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* STILL NEED TO FINISH PREVIOUS CORRECTIONS 1, 4, 5, 7 FROM PREVIOUS LIST ON ROOF, SEAL UNUSED RACEWAYS. |
|
| 04/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. IDENTIFY "SERVICE DISCONNECTS" AS SUCH -- NEC 230.70B 2. SECURE GROUNDING ELECTRODE CONDUCTORS TO STRUCTURE -- NEC 110 3. CORD FOR HOOD NEEDS CONNECTOR -- NEC 400.10, 400.14 4. INSTALL APPLIANCES (RANGE) 5. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED -- NEC 408.4 (MICRO, REFRY?) 6. PROVIDE DISCONNECTING MEANS FOR WATER HEATER - NEC 422.31B 7. HAVE SEVERAL LOOSE RECEPTACLES -- NEC 406.4 8. ALL UNITS TO BE UNLOCKED FOR INSPECTION AND PROVIDE ROOF ACCESS (LADDER). CHECK ALL OTHER BUILDINGS FOR THESE CORRECTIONS BEFORE YOU CALL THEM IN PLEASE, CALL EACH BUILDING IN AT A TIME, AS IT IS FINISHED NOT ALL AT ONCE. |