Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 02/02/2006 | FRAMING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection No change from 1/30/06-You must comply Refee imposed-You must pay a reinspection fee within 5 days |
|
| 01/30/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 14" DUCT SUPPLY TO SECOND FLOOR RESTRICTED (MORE THAN 1/3) EITHER REDUCE RESTRICTION OR HAVE A MECHANICAL ENGINEER DOCUMENT AS BUILT AND CERTIFY MECHANICAL SYSTEM COMPLIANCE - HAVE CERTIFICATION APPROVED BY C.O.T 2. F5A TRUSS REPAIR NOT MADE - NEXT FAILURE WILL REFF |
|
| 01/27/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 2 AND 4 OF 1/25/06 NOT DONE 2) OK TO INSULATE |
|
| 01/25/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE 1" CLEARANCE TO COMBUSTIBLE AT WATER HEATER B-VENT 2) F5A TRUSS DAMAGED. PROVIDE CITY APPROVED ENGINEERING REPAIR 3) NAIL PROTECT PEX GARAGE 4) 14" DUCT RESTRICTED AT 2ND FLOOR MAX OVER 9'-3" 5) REVERSE PITCH ON WATER HEATER B-VENT 6) PEX MUST BE 6" TO B-VENT 7) NAIL PROTEC A/C 220 |
|
| 01/23/2006 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) FIRESTOP GARAGE CHASE 2) 1" TO COMBUSTIBLE AT WATER HEATER B-VENT 3) NO GAS TEST 4) NO DWV WATER TEST 5) STOPPED INSPECTION 6) HOUSE NOT COMPLETE |