Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 11/02/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PROOF OF MECHANICAL APPROVAL |
|
| 11/01/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ENGINEERS-NO REPAIR DOCUMENT FOR F-3 TRUSS DAMAGE TAKEN FOR FILE 2) EXTERIOR CLIP NOT APPROVED |
|
| 10/18/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEM #10 FROM 10/12/05 INSPECTION NOT DONE |
|
| 10/13/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) KITCHEN G-1 SHEARWALL NOT PER PLAN |
|
| 10/12/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEWER DRAIN MUST HAVE 1/4" PER FOOT PITCH 2) GARAGE P-1 SHEAR WALL REQUIRES AB'S AT 16" ON CENTER 3) STAIR STRINGERS NOT PER 53/AD-3 4) F2A TRUSS NOT BEARING ON HEADER 5) NO DWV WATER TEST 6) LAUNDRY EXHAUST MUST GO OUTSIDE 7) FIREBLOCK 2ND FLOOR GARAGE 8) FIRE STOP WATER HEATER B-VENT 9) SECURE BEDROOM ELECTRIC BOX 10) F3 TRUSS TOP PLATE CUT OVER GARAGE/TOILET 11) FIREBLOCK STAIRS |
|
| 10/07/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) ITEM 04035 NOT APPLICABLE PER PAPERWORK TURNED IN BY INSPECTOR J. RIVA |