Permit: T05CM02219

Parcel: 140376630


Addresses:

6877 S HARRIER LP

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
02/28/2006 BUILDING - FINAL Approved IVRS - Inspection :*
1) OUT OF SEQUENCE INSPECTION REQUESTED BY H. LEYVA
2) APA RECEIPT #R0603942 ATTACHED
02/27/2006 BUILDING - FINAL Denied ITEMS 1, 4 AND 7 FROM PRIOR 2/23/06 INSPECTION NOT DONE
YOU MUST PAY REINSPECTION FEE
02/23/2006 BUILDING - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) ALL GARAGE CONVENIENCE ELECTRIC OUTLETS MUST BE GFCI PROTECTED
2) SEAL WALL PENETRATIONS IN GARAGE WITH DRYWALL AND HARD SET MUD NOT JUST TAPE
3) REVERSE PITCH ON FURNACE B-VENT
4) PROVIDE FURNACE MODEL 58DLA 090 INSTALLATION MANUAL
5) REVERSE PITCH ON PRIMARY CONDENSATE DRAIN
6) CHECK FURNACE MANUAL FOR B-VENT CONNECTION
7) CONVENIENCE OUTLETS NOT ALLOWED UNDER COUNTER OVER HANG OF MORE THAN 6"
02/14/2006 BUILDING - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) TRIM CLEANOUTS TO GRADE
2) DRYER FLAP WILL NOT SEAL/CLOSE
3) REMOVE STUCCO TIE WIRE
4) OUTSIDE HOSE BIBS REQUIRE ANTI-SIPHON VALVES
5) STOPPED INSPECTION-TOO MANY ITEMS
02/07/2006 BUILDING - FINAL Cancelled CANCELLED PER ANNE SUPERINTENDENT OF K.B. HOMES #548-7008
02/07/2006 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*