Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/20/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 12/19/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) A/C WIRES NOT NAILED PROTECTED-WIRES LESS THAN 1 1/4" TO PLATE SURFACE-REPEAT ITEM 2) A REFEE HAS BEEN IMPOSED, YOU HAVE 5 DAYS TO PAY REFEE |
|
| 12/16/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIREPLACE FIRE STOP/? NOT INSTALLED PER INSTALLATION MANUAL FIGURE 34. REMOVE INSULATION CENTER DUCTWORK IN CHASE AND INSTALL FIRESTOP SPACER PROVIDE 2" CLEARANCE TO WOOD 2) REMOVE INSULATION FROM TOP PLATE AREAS WHERE WIRES PENETRATE TOP AND BOTTOM WALL PLATES. INSTALL NAIL PROTECTION AS NECESSARY 3) USE ONLY SV4.5HF 3) SPACER COLLAR ONLY FOR FIREPLACE INSTALLATION |
|
| 12/12/2005 | FRAMING | Cancelled | CANCELLED PER TIM OF K.B. HOMES #907-6040 | |
| 12/08/2005 | FRAMING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection Secure wires within 8" of electric box Seal second floor penetration Provide water test of tub-install seal F-3 trusses not bearing at mid point Fireplace vent seal plate not installed per figure 17 of installation manual Nail protect wires within 1 1/4" of stud plate surface You have 5 days to pay a reinspection fee |
|
| 12/07/2005 | FRAMING | Cancelled | IVRS - RI canceled | |
| 12/06/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NO DWV WATER TEST 2) NO GAS PRESSURE TEST 3) 1" CLEARANCE REQUIRED TO COMBUSTIBLE ABS PLUMBING AT WATER HEATER VE?T 4) INTERIOR BEARING WALLS NOT BEARING TRUSSES 5) INTERIOR BEARING WALLS REQUIRE DBL TOP PLATES 6) STOPPED INSPECTION-NEXT FAILURE WILL REFEE |
|
| 12/05/2005 | FRAMING | Cancelled | CANCELLED PER TIM OF K.B. HOMES #907-6040 | |
| 11/28/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) CS20 STRAPS MISSING IN GARAGE SHEARWALL 1/SD2 2) GAS LINE NOT COMPLETE AT FIREPLACE 3) 1" CLEARANCE REQUIRED TO COMBUSTIBLES MATERIAL AT WATER HEATER 4) STOPPED INSPECTION 5) SUPERINTENDENT TO INSURE HOUSE IS COMPLETE PER PLAN AND CODE PRIOR TO NEXT INSPECTION |