Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 10/22/2005 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* | |
| 10/19/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 11/SD4 NOT COMPLIED WITH AT S.E. CORNER 2) 2ND FLOOR P-1 SHEAR PANEL MUST BE 8 FEET LONG 3) MBR WINDOWS NOT PER PLAN 4) KING STUDS AT WINDOWS TO SHORT 5) SHEAR OSB NOT NAILED PER PLAN 6) PROVIDE HEADER POST DETAIL DETAIL FOR 5050 MASTER BEDROOM WINDOW 7) ENTRY HEATER REQUIRES 2-2 X 4 POST 8) REPLACE P-3 SLABBED SILL PLATE WITH 2 X 6 PLATE 9) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF PLATE EDGES 10) ROOF NOT NAILED-NAIL ENDS 6" ON CENTER STAPLES 4" ON CENTER 11) 2 X 6 P-3 SHEAR WALL REQUIRES 2 X 6 DBL TOP PLATE |