Permit: T05CM02214

Parcel: 140378440

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/16/2006 FRAMING Approved IVRS - Inspection :*
02/13/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 1, 2 AND 4 FROM 2/9/06 NOT DONE
2) SEAL 2ND FLOOR PENETRATIONS
3) PROVIDE 1" CLEARANCE TO COMBUSTIBLE AT WATER HEATER VENT ROOF FILL HOLE IN ROOF
4) NO SECOND FLOOR DWV TEST
5) RED HEAD NACHOR BOLTS LOOSE AND MISSING
02/09/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WATER SERVICE KINKED AT EXTERIOR WALL
2) SHORT STUDS GARAGE
3) LEAK PEX LAUNDRY
4) FIRE BLOCK STAIRS BELOW STRINGER
5) ACCESS TO INSPECTION BLOCKED BY DRYWALL
6) NAIL PROTECT WIRES
7) STOPPED INSPECTION-TO MANY ITEMS
02/06/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECURE H20 SERVICE AT EXT. WALL
2) SHIM UNDER STUDS TO SHORT N/WALL GARAGE
3) VENT FOR 2ND FLOOR SHOWER DOES NOT GO HORIZONTAL UNTIL SIX INCHES ABOVE FLOOD RIM
4) ZERO GAS TEST
5) SECURE 2400 AT BLACK #8 ABOVE NICHE KITCHEN AT METAL GUSSETT
6) RANGE VENT OUT OF WALL
7) REAR HOSE BIB H20 LINE AT BANG PLATE EDGE
8) CLAMP GAS LINE AT EXT WALL
9) HOLE IN ROOF AT H20 HTR FLUE
10) NEED POTABLE TEST, REDUCER BUSHING AT H20 SERVICE METER NOT SIZED TO HUB
11) BLOCKS AT TUB SIDES
12) TRUSS CUT ROOF NEED REPAIR